Memória de Cálculo da Carga Térmica Para um Supermercado
Por: Gil Filho • 20/3/2023 • Projeto de pesquisa • 4.592 Palavras (19 Páginas) • 66 Visualizações
Air System Sizing Summary for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Zone Sizing Summary for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Air System Design Load Summary for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Zone Design Load Summary for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Space Design Load Summary for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
System Psychrometrics for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Psychrometric Analysis for COMERCIAL - LOJA 01
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Air System Sizing Summary for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Zone Sizing Summary for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Air System Design Load Summary for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Zone Design Load Summary for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Space Design Load Summary for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
System Psychrometrics for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Psychrometric Analysis for COMERCIAL - LOJA 02
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:13
Psychrometric Analysis for COMERCIAL - PRAÇA ALIMENTA
Project Name: YROYAK 06/21/2021
Prepared by: Mec Nav Engenharia 07:16
Air System Information
Air System Name COMERCIAL - LOJA 01
Equipment Class SPLT AHU
Air System Type SZCAV
Number of zones 1
Floor Area 49.1 m²
Location Manaus, Brazil
Sizing Calculation Information
Calculation Months Jan to Dec
Sizing Data Calculated
Zone L/s Sizing Sum of space airflow rates
Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 16.7 kW
Sensible coil load 13.1 kW
Coil L/s at Jan 2100 1135 L/s
Max block L/s 1135 L/s
Sum of peak zone L/s 1135 L/s
Sensible heat ratio 0.787
m²/kW 2.9
W/m² 340.0
Water flow @ 5.6 °K rise N/A
Load occurs at Jan 2100
OA DB / WB 29.9 / 27.1 °C
Entering DB / WB 24.7 / 18.8 °C
Leaving DB / WB 15.0 / 14.5 °C
Coil ADP 14.0 °C
Bypass Factor 0.100
Resulting RH 55 %
Design supply temp. 14.4 °C
Zone T-stat Check 1 of 1 OK
...